Energy consumption meter 1-phase LE-01MB F&F
- Energy consumption meter 1-phase LE-01MB F&F
Energy consumption meter 1-phase LE-01MB F&F
Product description
Purpose
LE-01MB is a static (electronic) calibrated single-phase AC electricity meter in a direct circuit. It is used for indication and registration of consumed electricity and parameters of the supply network. It allows remote reading of indications through a wired network of the M-Bus standard. The meter is configured through the configuration menu, accessible from the front panel, and through the communication port in accordance with the software functions of the M-Bus.
Compliance
MID Directive 2004/22/EC
Certificate No. 0120/SGS0214
Functions
* 1-phase
* bidirectional (4-quadrant)
* direct measurement 100 A
* indication of kWh/kvar (consumed/devoted)
* indication of network parameters
* mID compliance
* m-Bus protocol
* pulse output SO
* backlit, multifunction LCD display
* counter configuration protection by password
Measured values
Active energy input/output | AE+/AE- | [kWh] |
Reactive energy consumed/generated | RE+/RE- | [kvarh] |
Phase voltages | U1, U2, U3 | [V] |
Phase currents | I1, I2, I3 | [A] |
Frequency | F | [Hz] |
Active power | P | [W] |
Reactive power | Q | [var] |
Apparent power | S | [VA] |
Power factor | cos? | |
Power demand |
Technical data:
Type | single-phase |
Ports | M-Bus |
Communication protocol | M-Bus |
Compliance | MID Directive 2004/22/EC, Certificate No. 0120/SGS0214 |
Reference voltage | 230 V AC |
Base current | 5 A |
Maximum current | 100 A |
Minimum measured current | 0,02 A |
Self-consumption of the meter | 10 VA; 2 W |
Counter indication range | 0÷99999.99 kWh |
Counter constant | 1, 10, 100, 1000 imp/kWh or 1, 10, 100, 1000 imp/kvarh |
Readout signaling | 2 x LED |
Accuracy class | B |
Rated frequency | 50 Hz |
Insulation protection class | Class II |
Pulse output kWh/kvarh | 2 x open collector |
Connection voltage kWh/kvarh | max. 27 V DC |
Connection current kWh/kvarh | 27 mA max |
Pulse time kWh/kvarh | 60, 100, 200 ms |
Measured voltage | 176÷276V AC |
Overload capacity | 30×lmax/10 ms |
Isolation | 4 kV/1 min; 6 kV/1 μs |
Pulse connections and communication | screw terminals 1.5 mm² |
Voltage and current connections | 16 mm² screw terminals |
Operating temperature | -20÷55°C |
Dimensions | 2 modules (35 mm) |
Mounting | on a 35 mm rail |
Protection class | IP51 |