Voltage relay with current control VA- 63AG3W
- Voltage relay with current control VA- 63AG3W
Voltage relay with current control VA- 63AG3W
Voltage relay VA-63A G3W with current control is designed to protect electrical devices and household appliances from unacceptable voltage fluctuations. The device continuously analyzes the mains voltage and, if it is exceeded, the connected devices are switched off, and the load is switched on automatically after the voltage returns to the preset range. The user sets the required upper and lower voltage limits and the time of the switch-on delay.
The switch-on delay is required for electrical devices that do not tolerate short power outages (refrigerators, air conditioners, etc.).
The device also monitors the current consumption of the connected load, as there are a number of abnormal situations occurring due to excess current: the most common is when the wiring heats up, the most critical is a "short circuit". If the maximum current is exceeded, the load is immediately turned off. The load is switched on by a button on the front of the device.
TrueRMS (new quartz resonator)
Thermal protection and internal temperature indicator
Red indicator (G3R version) / White indicator (G3W version)
New housing and handle
Capable of full zero transit (16mm2 busbar)
Programmable settings:
- Value of lower and upper voltage trip limit
- Load turn-on delay time
All preset values are stored in non-volatile memory.
Specifications
Single-phase
Rated load current: 63A
Maximum load current: 80A
Measured voltage: 50-400V
Shutdown time for upper limit: 0.02 sec.
Cut-off time for lower limit, no more than 1 sec (120V-200V) 0.02 sec (<120V)
Lower cut-off limit for voltage: 120-200V
Upper cut-off limit for voltage: 210-270V
Load turn-on delay time: 5-600s
Size: 2 modules
DIN rail mounting