F&F AT-3I current temperature transmitter
- F&F AT-3I current temperature transmitter
F&F AT-3I current temperature transmitter
Product description
Analog temperature transmitter for PT-100. current (4-20 mA).
The AT-3I transmitter is designed to measure temperature with an external PT-100 temperature sensor and convert the measured value to a unified analog current output signal in the range of 4÷20 mA.
Operation
The AT-3I transmitter continuously converts the resistance of the external temperature sensor to a DC output signal in the range of 4÷20 mA. As a result of the transformation, a current proportional to the temperature of the environment in which the temperature sensor is located appears at the output.
The module works with a PT-100 type temperature sensor.
Dedicated temperature probe manufactured by F&F: RT-56 probe. probe available separately.
The signal output of the module is protected by an anti-interference filter, which eliminates network interference that affects the accuracy of the transmitted signal. This allows the use of signal cables of up to 300 m in length.
Technical data:
Supply voltage | 9÷30 V DC |
Measurement range | -100°?÷100°? |
Temperature probe | RT56 (PT-100) |
Maximum measurement error | ±1,0°? |
Output signal | 4÷20 mA |
Conversion error | ±0,5% |
Signal output cable length | 300 m |
Connection | screw terminals 2.5 mm² |
Tightening torque | 0.4 Nm |
Power consumption | 0,8 W |
Operating temperature | -20÷50°C |
Dimensions | 1 module (18 mm) |
Mounting | on a 35 mm rail |
Protection class | IP20 |