CP-721 F&F 1-phase voltage relay
- CP-721 F&F 1-phase voltage relay
CP-721 F&F 1-phase voltage relay
Product description
The CP-721 voltage relay is used to control the voltage of a single-phase network and protect a single-phase load from the effects of voltage increases or decreases beyond the set values.
Functions
- Voltage window setting (UL and UH thresholds)
- Separate setting of tripping times when UL and UH thresholds are exceeded
- Return time setting
- Continuous display of the mains voltage value
- Signaling of correct network voltage and contact closure
Operation
In operating mode, the display shows the value of the currently measured voltage.
User-settable lower (UL) and upper (UH) voltage thresholds determine the so-called voltage window, within which changes in the supply voltage may occur without tripping the relay. At the correct supply voltage, the relay contact remains closed. A change in supply voltage above or below the set voltage thresholds will open the contact with a user-set time delay. The illumination of the red LED indicates the closed state of the contact. Voltage exceeding 5V from the set values of UH and UL thresholds is signaled by pulsation of the values shown on the display.
Reconnection of the relay contact will take place automatically in case of a permanent voltage value of 5 V in relation to the set threshold values UH and UL for a return time set by the user.
The relay can be energized up to 450 V~. This allows effective protection of the load even when the voltage rises above the permissible standards.The device is protected against the change of polarity of the power supply - this will not damage ("burn") the relay.
Technical data:
Type | single-phase |
Supply voltage | 150÷450 V AC |
Time lock | NO |
Cooperation with power generators | YES |
Output load capacity (AC-1) | 2 x 8 A |
Executive element | 2 × relay |
Contact configuration | 2 × NO/NC |
Contact separation | YES |
Contact status indication | LED red |
Display | 3 × segment LED 5 × 9 mm |
Setting accuracy | 1 V |
Measurement accuracy | ±1 V |
Tripping voltage thresholds / stroke - lower UL | 150÷210 V / 1 V |
Tripping voltage thresholds / stroke - upper UH | 230÷260 V / 1 V |
Return voltage hysteresis for UL/UH | 5 V |
Tripping time / stroke - for UL threshold | 2÷10 s / 1 s |
Tripping time / stroke - for UH threshold | 0.1÷1 s / 0.1 s |
Return time for UL/UH | 2 s÷9,5 min |
Connection | screw terminals 4.0 mm² |
Tightening torque | 0,5 Nm |
Power consumption | 0,8 W |
Operating temperature | -25 ÷ 50 °C |
Dimensions | 2 modules (35 mm) |
Mounting | on a 35 mm rail |
Protection class | IP20 |