PCR-513 F&F single function time relay
- PCR-513 F&F single function time relay
PCR-513 timer relay
Index to order: PCR-513 230V
Function: Delayed switching.
Timing relays are used for time control in industrial and home automation systems (e.g.: ventilation, heating, lighting, signaling, etc.).
Operation
When the supply voltage is applied, the contact remains in position 11-10 and the set time of operation is measured. After the countdown, the contact is switched to the 11-12 position. Re-execution of the relay operation mode is possible after the power supply voltage is disconnected and switched on again.
Attention!
* When the power supply is on, the system does not react to the change of the time range setting.
* Operation with the newly set time range takes place after the power supply is disconnected and switched on again.
* When the power supply is switched on in the set time range, it is possible to smoothly adjust the time within the range of the time setting value.
Time ranges
0,1s: |
0,1 |
0.1÷1.20 SEK
|
1s: |
1÷12 SEK
|
10s: 10 |
10÷120 SEK
|
1m: |
1÷12 min
|
10m: |
10÷120 min
|
2h: 2 |
2÷24 hrs
|
1d: |
1÷12 days (24÷288 hrs)
|
2d: 2 |
2÷24 days (48÷576 hours)
ON - when power is switched on, causes permanent switching of the contact in position 11-12.
OFF - when the power is on, it causes permanent switching of the contact in the 11-10 position.
Technical data
Power supply voltage |
230 V AC |
Operation mode |
delayed activation |
Executive element |
relay |
Maximum load current |
10 A |
Contact configuration |
1 × NO/NC |
Contact separation |
YES |
Contact status indication |
LED red |
Operation time - adjustable |
0.1 s ÷ 576 hrs. |
Power supply signaling |
LED green |
Connection |
screw terminals 2.5 mm? |
Tightening torque |
0,4 Nm |
Power consumption |
0,8 W |
Operating temperature |
-25 ÷ 50 °C |
Dimensions |
1 module (18 mm) |
Mounting |
on a 35 mm rail |
Protection class |
IP20 |