Phase sequence and phase loss sensor 1xNO/NC CKF-316 TRMS F&F
- The CKF-316 TrueRMS phase sequence and phase loss sensor is designed to protect electric motors powered from a three-phase network.
Phase sequence and phase loss sensor 1xNO/NC CKF-316 TRMS F&F
The CKF-316 TrueRMS phase sequence and phase loss sensor is designed to protect electric motors supplied from three-phase mains. The phase sequence and phase loss sensor will trip if there is a voltage loss in at least one phase or if there is voltage asymmetry between phases. That is, when there is a danger of destroying the motor. The CKF-316-TrueRMS also controls the order of the power supply phases, preventing the motor from spinning in the wrong direction
Operation
A voltage failure in at least one phase of any phase or a voltage asymmetry between phases above the trip threshold will cause the motor to shut down. The shutdown will occur with a delay of 4 s, which prevents accidental disconnection of the motor during a momentary voltage drop. Reconnection will occur automatically when the voltage rises by 5 V above the trip voltage (i.e., by the voltage hysteresis value). With the above anomalies, it is impossible to start the motor. In the event of a change in the sequence of phases in front of the sensor causing an undesirable change in the direction of rotation of the motor, the sensor will not allow the motor to start. Restarting is possible after the return of the correct phase order.
Thanks to the measurement of the real effective voltage value (TrueRMS), the sensor guarantees correct operation even in case of operation in a heavily disturbed power supply network.
Technical data:
Supply voltage | 3 × 400 V + N |
Cooperation with power generators | NO |
Phase loss / asymmetry control | YES |
Phase sequence control | YES |
Contactor contact monitoring | NO |
Executive element | relay |
Maximum load current | 10 A |
Contact configuration | 1 × NO/NC |
Contact separation | YES |
Tripping voltage asymmetry | 55 V |
Voltage hysteresis | 5 V |
Cut-off delay | 4 s |
Power control | 2 × LED |
Connection | screw terminals 2.5 mm² |
Tightening torque | 0.4 Nm |
Power consumption | 1,6 W |
Operating temperature | -25÷40°C |
Dimensions | 1 module (18 mm) |
Mounting | on a 35 mm rail |
Protection class | IP20 |
TrueRMS | YES |